Vol 33 – Control and Protection – System Overview (continued)

Master Class Banner - For Experts

The MasterClass series of articles have covered a wide range of topics, some related to specialised applications and some to standard components.  However, in some instances, the principles behind their selection have not been covered.  Therefore, before proceeding further into Capacity Control and the specific aspects of refrigeration and air conditioning, we have decided to look at a complete system (Figure 1 – Part 32) to summarise the content of certain preceding articles.  This work commenced in Part 32 and Part 33 now continues with this.

Liquid Line Solenoid Valve (LLSV)

We now arrive at the Liquid Line Solenoid Valve (LLSV). This valve facilitates the evacuation of liquid from the evaporator during the off-cycle i.e. when the thermostat de-energises the solenoid valve on reaching its set temperature. This valve provides a back-up safety feature by preventing liquid leaking through the TEV during the off-cycle.

Liquid Line Solenoid Valves are selected on the basis of the evaporator duty expressed in kW for a specific refrigerant and the Maximum Operating Pressure Differential (MOPD).  This is the highest pressure that will occur on the inlet to the valve minus the lowest pressure that will be found on the outlet of the valve. This MOPD must not exceed the manufacturers rating if the valve is to open correctly.

When reading selection data, ensure that it applies to the fluid passing through the pipe as it is not unknown for an engineer to select a valve for suction line use whilst reading data for discharge flow.

On larger plant it is well worth considering the use of solenoid valves fitted with a manual opening spindle. This is useful when diagnosing possible problems in the control circuit or proving the correct operation of the valve.

FIG 1

With this type of solenoid valve, the stem, 53, is screwed clockwise to manually open the valve.  The stem lifts the valve seat, 83, allowing fluid to pass through the valve.

Thermostatic Expansion Valve

We now reach the Thermostatic Expansion Valve. These valves are available with a number of functions which allows the requirement of a system to be closely matched.  Further data on expansion devices is available from within preceding articles.

Readers of this series will already know that a TEV modulates open or closed in response to  temperature variations at the evaporator suction outlet pipe / TEV phial strapped to the pipe. As the temperature increases, the pressure generated by the TEV phial refrigerant charge increases and this pressure is transmitted onto a diaphragm. The diaphragm bows and moves a push-rod that opens the inlet to the valve, thus allowing refrigerant to enter the evaporator.  The current evaporating pressure, which continually varies with instantaneous load, is transmitted to the underside of the diaphragm.  The difference between these two, coupled with the action of the spring, allows the control of superheat.

When the temperature falls, the pressure difference above and below the diaphragm is reduced to zero (the pressures on the diaphragms upper and lower surfaces are in equilibrium) and the only differential pressure now exerted is that generated by the superheat adjusting spring which closes the valve. See figure 2.

Figure 2

The type valve shown is an internally equalised valve. These valves are used when the pressure drop across the evaporator is less  than 0.25 bar. When the evaporator pressure drop exceeds 0.25 bar, an externally equalised TEV is used.  These valves have an external connection between the TEV and the evaporator outlet and this ensures that the pressure at the evaporator outlet is exerted on the underside of the diaphragm rather than that at the inlet which will be higher thus leading to inaccurate control of superheat.  If the temperature at the outlet is greater than the saturated pressure-temperature relationship then superheat will warm the phial and raise the pressure within the phial and start to modulate the valve open.

When calculating the pressure drop across the evaporator, the calculation should cover the run from the expansion valve outlet to the evaporator outlet.  Since all but the smallest evaporators will be fitted with distributors and distributor tubes, the pressure drop in these components must be taken into consideration. Typically these components are selected on the basis of a pressure drop of 0.5 bar.

TEV’s are selected on the basis of the evaporator duty, the type of refrigerant and the pressure drop that occurs between the receiver outlet and the evaporator inlet.  While on most air conditioning and single stage applications the amount of liquid sub-cooling will be insufficient to affect the valve selection, it should be born in mind that when mechanical sub-cooling is used, this can have a significant effect on the valve capacity and must be taken into consideration during the selection process.

Evaporator Pressure Regulator

The next component is an Evaporator Pressure Regulator. Although it would be unusual to find both an EPR and a Capacity Regulator (CPR) on the same system, it is not totally unknown. The EPR senses the evaporator pressure and modulates to close the suction line when the evaporator pressure starts to fall, while the CPR  valve by-passes discharge gas to into the suction when suction pressure falls.

In the configuration shown as Figure 1, the CPR valve is sized to match the duty of one evaporator or 1/3 rd the installed compressor capacity. This would be adequate to prevent short cycling and at the same allow a reduction in pressure of  the suction side when the load on the second evaporator begins to fall, thereby enabling a pressure sensor to switch off one compressor.

Although the suction pressure would fluctuate upstream of the EPR, the pressure downstream of the EPR would be maintained at a constant level thereby maintaining a constant evaporation temperature. If the pressure continued to drop upstream of the EPR, then the system controller would switch off one of the compressors.

The function of the discharge by-pass capacity pressure regulating valve (CPR) and its associated de-superheating expansion valve was covered in last months article.

An examination of Figure 1 shows that a Dual Pressure Relieving Valve (PRV) assembly is fitted to the suction line accumulator. Since the low side can be isolated from the high side and some high side relief valves are venting into the low side, precautions must be taken to protect the system if a fire occurred. Therefore, a relief valve assembly of sufficient capacity must be fitted to the low side. The location of this PRV can be anywhere on the low side as long as the connections to the PRV are of sufficient size to allow vapour to vent through and the PRV cannot be isolated from the system. In most cases this would be from a suction line accumulator or suction header if one is fitted.

Oil separators

The object of fitting an oil separator is to reduce the amount of oil carried over into the system thereby leading to reduced oil level in the crankcase of the compressor(s). This oil is entrained in the discharge gas as it is pumped from the compressor(s). It should be noted that oil separators reduce the amount of oil carried over into the system, no oil separator is guaranteed to be 100% efficient.

Oil is required to lubricate the moving parts of the compressor.  It is not required anywhere else in the system.  Oil is an insulator and in fact reduces the efficiency of all the heat exchange surfaces that it comes into contact with.  Moreover, it can be argued that a small percentage of the energy expended by the compressor is dedicated to pumping this oil and that the overall mass flow of refrigerant throughout the system is reduced.

Oil separators which are connected to condensers that are located vertically above them should be fitted with a check-valve in their outlet . This check valve is to prevent liquid refrigerant that can condensed in the discharge line to the condenser, draining back into the separator and mixing with the oil. If this occurs, refrigerant rich oil is fed back to the compressor where the oil will foam.  This will displace the oil from the crankcase. When this occurs, compressor lubrication fails and the compressor either will trip out on via the safety switch or more seriously, the bearings will be damaged.

Systems that have long off cycles, particularly during winter, should have a heater fitted either in or around the oil separator. This heater will evaporate any liquid refrigerant that condenses within the separator. The heater should be inter-locked with the motor contactor which should be arranged to energise the heater whenever the compressor motor switches off.  This can be achieved via the auxiliary contacts of the contactor.

Most conventional oil separators separate the oil from the discharge vapour by reducing the velocity of the vapour to a level which is below its ability to carry droplets in the vapour stream.  The discharge vapour then passes through a mesh which assists in the removal of the oil droplets and at the same time acts as a filter to remove any sediment that may be in the system. With this type of separator it is important not to exceed the design capacity of the separator, otherwise the correct oil drop out velocity will not be achieved.

Whilst the above method of oil separation is possibly the most common, there are other types of oil separators which operate on different principles.  The manufacturers of these claim certain advantages and among these are the Helical and Coalescent separators.

Helical Oil Separator

An oil separator which works on a diametrically opposite method of separation is the Helical Oil Separator.  This separator uses the centrifuge principle to separate the oil from the discharge vapour.  The separator converts the flow of the discharge vapour into a high velocity spiral path created by helical wound fin which forces the vapour to spin. Centrifugal force causes the heavier oil particles to be thrown against the wall of the separator where they drain down to the base of the chamber. A baffle over the oil collecting sump prevents the oil from becoming entrained in the discharge vapour. With this type of separator it is essential that  the duty does not fall below 50% of the rated capacity since the centrifugal effect would then be lost.

Coalescent Oil Separator

The third type of oil separator covered is a comparatively new type called a Coalescent Separator. This separator relies on the ability of Borosilicate glass fibre to excite (vibrate) oil molecules causing them to collide with each other and form (Coalesce) into larger droplets These droplets are forced through the filter where they collect and drain by gravity into the oil separator sump. The glass fibre filter used with this type of separator is extremely fine with the ability to filter down to 0.3 microns which is half the diameter of cigarette smoke.

Because of the fine filtration created by the glass fibre, the level of filtration is finer than liquid or suction line filters which typically can filter down to 20 microns.  These separators can therefore clean up a system if it is contaminated and the manufacturers claim it may even reduce the need for an oil change if a burn out occurs.

Fig 3

NEXT MONTH: Part 34 – CAPACITY CONTROL

DISCLAIMER:  Whilst every effort is made to ensure absolute accuracy, Business Edge Ltd. will not accept any responsibility or liability for direct or indirect losses arising from the use of the data contained in this series of articles.

1 Comment

Leave a Reply

Main Menu